AGENDA MEMORANDUM                Item No.       4b 
ACTION ITEM                   Date of Meeting   September 26, 2017 
DATE:    September 18, 2017 
TO:     Dave Soike, Interim Executive Director 
FROM:   Jeffrey Brown, Director Aviation Facilities and Capital Programs 
Wayne Grotheer, Director Aviation Project Management Group 
SUBJECT:  Arc Flash Mitigation (CIP #C800826) 
Amount of this request:          $7,383,000 
Total estimated project cost:       $7,533,000 
ACTION REQUESTED 
Request Commission authorization for the Executive Director to (1) prepare design and
construction bid documents for the Arc Flash Mitigation project at Seattle-Tacoma International
Airport; (2) advertise and award a major works construction contract; and (3) utilize Port of
Seattle crews and small works contracts to perform construction work. The amount of this
request is $7,383,000 for a total estimated project cost of $7,533,000. 
EXECUTIVE SUMMARY 
Recent changes to the National Electrical Code (NEC) require the study, determination and
labeling of Arc Flash hazards present in electrical power distribution equipment and facilities.
Arc Flash is a type of electrical explosion or uncontrolled discharge of energy that results from a
low impedance connection through the air to ground or another phase of an electrical system. 
The Port's Arc Flash studies at the airport have shown that in some locations the arc flash
hazards need to be reduced as they exceed levels which can be managed by use of personal
protective equipment (PPE) worn by personnel working in the vicinity of the electrical
equipment. 
This project will mitigate all known arc flash hazards that exceed PPE limits within the Sea-Tac
airport power distribution system. The reduction in arc flash energy levelswill be achieved by 
replacing existing fuses with vacuum circuit breakers and by upgrading protective relays.  The
circuit breaker and protective relays provide adjustable and highly flexible "trip" settings
allowing for greatly improved coordination between upstream and downstream protective
devices within the power distribution network. The circuit breaker and protective relay
combination can also be adjusted to minimize the energy that can be transmitted during an arc
flash event.

Template revised September 22, 2016.

COMMISSION AGENDA  Action Item No. _4b___                    Page 2 of 6 
Meeting Date: September 26, 2017 
The arc flash evaluation studies are ongoing, and while additional severe arc flash hazard levels
may be discovered, we do not anticipate that additional capital projects will be required.
Aviation Facilities and Infrastructure expects to lower any new excessive arc flash hazard levels
by adjusting equipment settings.
In addition to reducing arc flash hazards to an acceptable level; this project will installinfrared 
(IR)  inspection windows allowing  for the annual inspection of electrical connections and
potential hot spots without requiring human exposure to energized equipment. IR windows
provide a safe method for inspection, eliminate the need for outages, and reduce the total time
required to perform the inspection.

JUSTIFICATION 
Improved power reliability avoids outages, equipment damage, failures and interruption of
critical operations. This project maximizes system reliability by providing the Port of Seattle
aviation maintenance staff with the safe working environment necessary to properly maintain
and operate the Sea-Tac Airport electrical distribution system. 
The Port's arc flash studies at the airport revealed arc flash incident energy levels to be as high
as 120 calories per square centimeter (cal/cm2) in some locations. The highest level set by the
National Fire Protection Association (NFPA) is 40 cal/cm2; this corresponds to the highest rated
PPE. This project will reduce arc flash energy levels to approximately 25 cal/cm2 in airport
electrical equipment and facilities. 
Electrical switchgear which exceeds the PPE limits cannot be serviced without power shut
downs. The regular shutdown of Airport operations to allow for routine electrical maintenance
and switching cannot be accommodated; therefore ,  essential system maintenance and
functions will not be possible without the completion of this project.

DETAILS 
This project is requesting a single authorization for both the design and construction phases of
work. A single authorization reduces staff time, soft costs, and will minimize the time required
to complete this project. 
To more accurately estimate the total project cost and facilitate a single Commission
authorization, the team took this project to 30% design completion during the project definition 
(Notebook) phase. The project cost estimate increased from the original concept approval
primarily due to the actual cost of the fuse to breaker retrofit conversions, which were more
complex than originally conceived. 

Template revised September 22, 2016; format updates October 19, 2016.

COMMISSION AGENDA  Action Item No. _4b___                    Page 3 of 6 
Meeting Date: September 26, 2017 
The project will phase all work to eliminate or minimize operational impacts.
Cooling Tower power center work will be completed in the winter months to reduce or
eliminate impacts to passenger comfort. 
Scope of Work 
This project will provide for the design and construction of all elements necessary to reduce
and or mitigate arc flash hazards at power distribution switchgear located throughout Sea-Tac
airport.  The scope of work for this project has not increased from the original concept and cost
estimate. The cost estimate to deliver this project has increased due to complexities with the
fuse to breaker conversions.
New replacement equipment includes: 
1.  Replace fuses in Power Centers with Vacuum Circuit Breaker: 
a.  C1 Building Power Center 
b.  Concourse C Power Center 
c.  Parking Garage Electrical Room 
d.  Concourse D Power Center 
e.  Cooling Tower Power Centers #1 through #5.
2.  Upgrade/replace relays feeding the Central Terminal Power Center to adjustable relays
with maintenance mode. 
a.  Set protective relays to minimize arc flash energy and coordinate with upstream
and downstream devices. 
3.  Addition of infrared windows in existing Power Centers included in item #1. 
Small Business 
Although this project requires highly specialized contractors, the project management team is
collaborating with the Port's Small Business group to identify and outreach to, possible small
businesses that would be able to compete for these opportunities within the above scope of
work. 
Schedule 
Activity 
Design start                        2017 Quarter 3 
Construction start                    2018 Quarter 3 
In-use date                        2019 Quarter 4 
Cost Breakdown                         This Request       Total Project 
Design                                  $1,224,000         $1,274,000 
Construction                              $6,278,000         $6,278,000 

Template revised September 22, 2016; format updates October 19, 2016.

COMMISSION AGENDA  Action Item No. _4b___                    Page 4 of 6 
Meeting Date: September 26, 2017 
Total                                       $7,383,000          $7,533,000 
ALTERNATIVES AND IMPLICATIONS CONSIDERED 
Alternative 1  Do not install arc flash mitigation measures 
Cost Implications: $150,000 (expense) 
Pros: 
(1)   No additional investment required 
Cons: 
(1)   Equipment cannot be maintained without disruption to airport operations. 
(2)   Maintenance staff will be unable to identify problem areas, which could lead to
extended outages. 
(3)   Preventative maintenance will not be possible at some locations, leading to shortened
equipment life and reduction in power reliability 
(4)   Poor response time for unplanned outages 
This is not the recommended alternative. 
Alternative 2  Install new protective relays at all locations with "maintenance mode" feature
on feeders in the terminal distribution power centers.
Maintenance mode is not equivalent to scope item #2 above, which is a permanent condition
enhancing the operational efficiency of the Power Distribution system. Maintenance mode is a
temporary condition that will diminish the capacity of the power distribution system while it is
enabled.
Cost Implications: $4.2M to $5M 
Pros: 
(1)   Reduced capital cost 
(2)   Reduces arc flash hazard levels to safe levels during maintenance mode 
Cons: 
(1)   Protective devices at Power Centers are not coordinated during maintenance mode
leaving the power distribution system temporarily vulnerable to wide spread system
outages 
(2)   Requires system outages on double-ended switchboards prior to working on the
equipment, significantly increasing the response time in the event of an unplanned
outage 
(3)   Requires installation of remote indicating device showing gear in maintenance mode 
(4)   Requires planned outages to perform project installation work 
(5)   Increase labor costs for maintenance and scheduled work 
This is not the recommended alternative. 

Template revised September 22, 2016; format updates October 19, 2016.

COMMISSION AGENDA  Action Item No. _4b___                    Page 5 of 6 
Meeting Date: September 26, 2017 

Alternative 3  Design, procure, and install Arc Flash Mitigation Measures at Power Centers
C1.2, C2, D, parking garage electrical room and Cooling Tower #1, #2, #3, #4 and #5. 
Cost Implications: $7,533,000 
Pros: 
(1)   Reduces arc flash hazard to NFPA required levels 
(2)   Permits compliance with NEC for annual visual infrared inspections 
(3)   Adds selective power coordination, i.e. faults are isolated to the nearest upstream
device eliminating unnecessary power outages
(4)   No impacts to airport operations 
(5)   Minimizes response time in the event of an unplanned outage 
(6)   Integrates with future SCADA project 
(7)   Allows new construction to occur with fewer operational issues 
Cons: 
(1)   Highest cost solution 
This is the recommended alternative. 
FINANCIAL IMPLICATIONS 
Cost Estimate/Authorization Summary          Capital      Expense        Total 
COST ESTIMATE 
Original estimate                      $3,200,000          $0    $3,200,000 
Current change                      $4,302,000      $31,000    $4,333,000 
Revised estimate                      $7,502,000      $31,000    $7,533,000 
AUTHORIZATION 
Previous authorizations                   $150,000           0      $150,000 
Current request for authorization           $7,352,000      $31,000    $7,383,000 
Total authorizations, including this request     $7,502,000       $31,000    $7,533,000 
Remaining amount to be authorized             $0         $0         $0 
Annual Budget Status and Source of Funds 
This project was included in the 2017  2021 capital budget and plan of finance with a budget
of $3.2 million. The budget increase will be transferred from the Aeronautical Allowance CIP
(C800753) resulting in no net change to the Aviation capital budget. The funding source will be
the Airport Development Fund. 
Financial Analysis and Summary 
Project cost for analysis         $7,533,000 
Business Unit (BU)            Terminal Building 

Template revised September 22, 2016; format updates October 19, 2016.

COMMISSION AGENDA  Action Item No. _4b___                    Page 6 of 6 
Meeting Date: September 26, 2017 
Effect on business performance   NOI after depreciation will increase 
(NOI after depreciation) 
IRR/NPV (if relevant)           N/A 
CPE Impact                $0.02 by 2021 
Future Revenues and Expenses (Total cost of ownership) 
This project supplements existing electrical distribution equipment  and  does not have a
material impact on the current Aviation Maintenance O&M costs. 

ATTACHMENTS TO THIS REQUEST 
None 
PREVIOUS COMMISSION ACTIONS OR BRIEFINGS 
None 












Template revised September 22, 2016; format updates October 19, 2016.

Limitations of Translatable Documents

PDF files are created with text and images are placed at an exact position on a page of a fixed size.
Web pages are fluid in nature, and the exact positioning of PDF text creates presentation problems.
PDFs that are full page graphics, or scanned pages are generally unable to be made accessible, In these cases, viewing whatever plain text could be extracted is the only alternative.